Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T00CM04229
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/12/2001 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000*1.) ALL CORRECTION MADE OK 2.) PLEASE DO NOT COVER UNTIL OFTEN INPSECTION 3.) WATER TEST OK 4.) OK TO COVER. | |
07/10/2001 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*WATER TEST ONLY REQ FOR INTERMEDIATE 1.) GATE WAS LOCKED | |
07/06/2001 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) FORM STAKE REPAIR MADE OK 2.) SYSTEM LOST GALLONS IN 30 MIN. MAKE SURE SYSTEM WILL HOLD TEST, OR REPAIR LEAKS, AND RECALL FOR INSPECTION. | |
07/05/2001 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) OVERHEAD GAS PIPING OK NEED TO SEE FINAL PIPING AND CONNECTION TO DRYERS 2.)COPPER IN WALLS AND OVERHEAD OK PRESSURE TEST OK 3.) TRAP ARMS TO LAVATIORIES MUST HAVE "A PER FOOT GRADE 4.) 1002.2 DEVELOPED LENGHT OF A TRAP ARM SHALL NOT BE LESS THAN 2 PIPE DIAMETER (O) FROM TRAP WIER TO POINT OF VENT. | |
07/03/2001 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999* | |
07/02/2001 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*NOT READY FOR INSPECTION | |
06/29/2001 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*1.) NOT READY FOR INSPECTION |