Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T00CM04229
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/01/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
10/26/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*PARTIAL @ LAUNDRY SIDE.1.) INSTALL A MAIN BORDING JUMPER AT NEUTRAL IN GUTTER TO GUTTER 2.) INSTALL ALL BOND SCREW INTO 30 AMP DISCONNECT 3.) PANEL 'P' DISCONNECT DOOR MUST OPEN AT LEAST 90 MOVE DISCONNECT 4.) LOOSE GROUNDING CONNECTIONS. | |
06/28/2001 | ELECTRIC - FINAL | Denied | NO ACCESS TO INTERIN |