Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING PRE-SLAB
Permit Number - T00CM04216
Inspection Description - BUILDING PRE-SLAB
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/26/2000 | BUILDING PRE-SLAB | Approved | IVRS - Inspection 0000* | |
10/25/2000 | BUILDING PRE-SLAB | Denied | IVRS - Inspection 0999*/1. PLAN CALLS FOR ADDITION TO BE 4' FROM WEST PROPERTY LINE. ONLY 3'-0" EXISTS BETWEEN SLAB AND WEST SIDE OF MASONARY WALL. EITHER PROVIDE PROOF OF PROPERTY LINE. (SURVEY STAKES AT WEST CORNERS) OR REVISE PLAN TO 3' SIDE SET BACK. 2. REINFORCEMENT STEEL IN CONTACT WITH SOIL. MUST BE A MINIMUM OF 3" FROM SOIL. 3. PROVIDE PERMIT FOR MASONRY PARTY WALL IN EXCESS OF 5 FEET HIGH ON WEST PROPERTY BOUNDARY. |