Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/16/2000 | PLUMBING - ABOVE CEILING | Approved | IVRS - Inspection 0000* ALL PLUMBING ABOVE CEILING OK GAS PIPING (ROUGH) OK PRESSURE TEST OK GAS PIPING INSTALLED PER PLAN IS SERIOUSLY OVERSIZED CONTRACTOR WILL REDUCE 4" GAS AT ROOF LEVEL TO 2" AND RUNDOWN WALL 2" TO METER APPROVED BY R MYERS |