Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/30/2001 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 11/01/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) HOSE BIB SOUTH SIDE OF HOUSE MISSING VACUUM BREAKER 2) DRYER VENT MISSING FLAPPER 3) GFCI LEFT SIDE OF SINK SHOWING OPEN NEUTRAL 4) PROVIDE FIRE SPRINKLER CERTIFICATION 5) STOPPED INSPECTION |