Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/14/2001 |
EXT METAL CLIPS/EXT SHEATHING |
|
Approved |
IVRS - Inspection 0000* |
| 02/21/2001 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/1. FURNACE VENT REQUIRES 1" CLEARANCE TO COMBUSTIBLE MATERIAL. 2. EAST TRUSS CLIP NOT NAILED. 3. BATHROOM SILL PLATES LOOSE. 4. TUBS EXCESS OF 5' TO DRAIN TRUNK REQUIRE CLEAN OUTS. 5. PLUMBING DRAINS AT TUBS NOT PER PLAN. REVISE PLAN TO AS BUILT. 6. FIRE BLOCK ALL DROP CEILINGS. 7. W/C FLOOR FLANGES NOT INSTALLED. 8. EXCESS OF 24" TO KITCHEN COUNTER OUTLET--RT OF SINK. 9. GABLE END TRUSSES EXCESSIVELY NOTCHED FOR LOOK OUTS PROVIDE CITY APPROVED TRUSS ENGINEERS REPAIR. 10. TRUSS AT LAUNDRY ROOM NOT CLIPPED. 11. GABLE END TRUSSES MUST BE CLIPPED TO EXTERIOR WALL AT ENDS AND EVERY 32" O.C. 12. MECHANICAL DUCT WORK NOT PER PLAN REVISE PLAN TO AS BUILT AND HAVE APPROVED BY C.O.T. |
| 01/23/2001 |
EXT METAL CLIPS/EXT SHEATHING |
|
Partial Approval |
MANY TRUSSES MISSING H 2.5 CLIPS ON SOUTH WALL CARPORT AND LAUNDRY. |