Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/16/2000 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 11/15/2000 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/1. ELECTRIC SUB PANEL MUST HAVE AN ISOLATED NEUTRAL BAR. 2. HEATER MUST BE ON A 20 AMP 220V CIRCUIT (BEDROOM SUBPANEL). |
| 11/14/2000 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/1. HOUSE NEED 4221 ADDRESS IN 3" MINIMUM HIGH NUMBER ON HOUSE. 2. EACH EXISTING BEDROOM AND ADDITION AS WELL AS ROOMS OR HALLS LEADING TO BEDROOMS MUST HAVE AT LEAST BATTERY OPERATED SMOKE DETECTORS LOCATED AT LEAST 18" FROM CORNERS AND 36" FROM AIR REGISTERS 3. BASEBOARD HEAT NOT IN 4. OUTLET AND SWITCH COVERS REQUIRED. |