Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T00CM04134
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/18/2000 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
12/15/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0235* INSPECTOR DAN SANTA CRUZ HAS REQUESTED THAT THE RECEPTACLES LOCATED IN THE JUNCTION BOXES BELOW THE FLOOR LEVEL FOR SERVICE TO THE PATIENT CHAIRS BE GFI PROTECTED OR STANDARD GFI RECPTACLES. THIS IS REQUESTED AS A PRECAUTIONARY ACTION DUE TO THE LIKELY HOOD OF WATER (WHETHER FROM CONTAINERS, WATER LINE, OR FLOOR CANE EQUIPMENT) ENTERING INTO THE BOXES AND POSSIBLE THE RECEPTACLES AND ANY CORD CONNECTED PLUGIN EQUIPMENT. THE NATIONAL ELECTRICAL CODE PROVIDES FOR THIS IN SECTION 517-20. CORRECT AND RECALL, INSPECTOR MAC CAPISTRAN |
|
12/14/2000 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* RECEPTACLE AND CIRCUITS IN 12X12" J-BOX SHOULD BE GFCI PROTECTED WATER CONNECTION MIGHT LEAK CAUSING THIS FLOOR TO GEZONE ENERGIZED |