Permit: T00CM04134

Parcel: 133243720

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T00CM04134

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/18/2000 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
12/15/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0235*
INSPECTOR DAN SANTA CRUZ HAS REQUESTED THAT THE RECEPTACLES LOCATED IN THE JUNCTION BOXES BELOW THE FLOOR LEVEL FOR SERVICE TO THE PATIENT CHAIRS BE GFI PROTECTED OR STANDARD
GFI RECPTACLES. THIS IS REQUESTED AS A PRECAUTIONARY ACTION DUE TO THE LIKELY HOOD OF WATER (WHETHER FROM CONTAINERS, WATER LINE, OR FLOOR CANE EQUIPMENT) ENTERING INTO THE BOXES AND POSSIBLE THE RECEPTACLES AND ANY CORD CONNECTED PLUGIN EQUIPMENT. THE NATIONAL ELECTRICAL CODE PROVIDES FOR THIS IN SECTION 517-20.
CORRECT AND RECALL, INSPECTOR MAC CAPISTRAN
12/14/2000 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
RECEPTACLE AND CIRCUITS IN 12X12" J-BOX SHOULD BE GFCI PROTECTED WATER CONNECTION MIGHT LEAK CAUSING THIS FLOOR TO GEZONE ENERGIZED