Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T00CM04112
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/04/2001 | FRAMING | Approved | IVRS - Inspection 0000* | |
12/29/2000 | FRAMING | Not ready for Inspection | IVRS - Inspection 0000*/1. MISSING A.B. AT INTERIOR SHEAR. 2. ALL DROP CIELINGS NEED RAT RUNS AT STURCTUAL B/CHORD 10' O.C. 3. GABLE END HINGE BRACES X DOWN/TO TOP PLATE 4. H.D. NOT TYPE SPEC'D ON PLAN 5. CAN'T READ SHEAR SCHEDULE, INK IS SMEARED. 6. NEED COMB/RELIEF DUCTS GARAGE. 7. MISSING GAS FLUES. 8. FILL ALL NAIL HOLES TRUSS CLIPS. 9. SECURE ALL H20 STUBS AT LAVS, TOLIETS ECT. 10. H20 LINE REFRIGERATOR OUT OF WALL (CHIP CONC.) MOVE BACK 11. INT. WALL STUD O.C. OVER SPAN CENTER ROOM N/SIDE AT HALL. |