Permit: T00CM04111

Parcel: 136261210


Addresses:

3067 S BECK DR

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
12/19/2000 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection 0000*
12/15/2000 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0999*/1. HOLDOWN AT GARAGE FRONT NOT NAILED. 2. STRAP CORNERS WITH OVERLAPPING DOUBLE TOP PLATES. 3. TRUSS DRAWINGS NOT ON SITE. 4. O.S.B. ROOF SHEATHING MUST SPAN 2 BAYS (3 TRUSSES). 5. O.S.B. PANELS CANNOT BE INSTALLED PARALLEL TO TRUSSES. 6. ROOF SHETHING LOOSE. RENAIL ALL SHINERS. 7. GABLE END BRACING MUST BE ANILED THRU SHEATHING. 6/DT1 ALSO AT SHEAR PANELS.
12/13/2000 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection 0000*/1. NEED TRUSS CALC'S AT SITE. 2. HPAHD NOT NAILED.
12/11/2000 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection NO PLAN ON SITE.