Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/15/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 03/14/2001 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 03/12/2001 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000*/1. UNCOVER ALL H.D.'S AT LATH. 2. INSTALL ALL MISSING H.D.'S 3. CHECK ALL PLATE BOLTS AT SHEAR WALLS AND AT NON SHEAR. 4. STRAP GAS LINE METER TO GARAGE WALL. 5. WEST BATH PEX OUT OF WALL. 6. H20 HEATER FLUE 1" CLR. TO COMB AND SECURE 7. GAS PIPE SIZED AND TEST HOLDING OK. |
| 03/07/2001 |
FRAMING |
|
Not ready for Inspection |
1. F/PLACE FRAMING, NOT PER INSTALLATION INSTRUCTIONS 2. GAS LINE SIZED, CHANGE OUT 1" TRUNK TO 1 1/4 AFTER DRYER, RANGE 3. TIGHTEN ALL H.D. NUTS 4. ADD 2 X 4 STUDS AT SHEAR WALL TO BE 16" O.C. 5. EXHAUST FAN REAR BATH, DUCT MISSING 6. H20 LINES, NEED TEST (PRESS). |
| 02/23/2001 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 01/23/2001 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |