Permit: T00CM04108

Parcel: 110101480

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
03/15/2001 FRAMING Approved IVRS - Inspection 0000*
03/14/2001 FRAMING Not ready for Inspection IVRS - Inspection 0000*
03/12/2001 FRAMING Not ready for Inspection IVRS - Inspection 0000*/1. UNCOVER ALL H.D.'S AT LATH. 2. INSTALL ALL MISSING H.D.'S 3. CHECK ALL PLATE BOLTS AT SHEAR WALLS AND AT NON SHEAR. 4. STRAP GAS LINE METER TO GARAGE WALL. 5. WEST BATH PEX OUT OF WALL. 6. H20 HEATER FLUE 1" CLR. TO COMB AND SECURE 7. GAS PIPE SIZED AND TEST HOLDING OK.
03/07/2001 FRAMING Not ready for Inspection 1. F/PLACE FRAMING, NOT PER INSTALLATION INSTRUCTIONS 2. GAS LINE SIZED, CHANGE OUT 1" TRUNK TO 1 1/4 AFTER DRYER, RANGE 3. TIGHTEN ALL H.D. NUTS 4. ADD 2 X 4 STUDS AT SHEAR WALL TO BE 16" O.C. 5. EXHAUST FAN REAR BATH, DUCT MISSING 6. H20 LINES, NEED TEST (PRESS).
02/23/2001 FRAMING Not ready for Inspection IVRS - Inspection 0000*
01/23/2001 FRAMING Not ready for Inspection IVRS - Inspection 0000*