Permit: T00CM04089

Parcel: 10408093A


Addresses:

625 W AUTO MALL DR

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
02/26/2001 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000$
02/23/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*
02/14/2001 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000* 1) NO TOOLS AVAILABLE TO ACCESS PANEL AND TRANSFORMER 2) LABEL PANELS 3) NEED MAIN BREAKER TO BE SECURED IN PLACE 384-16(G) *WILL CHECK THESE ITEMS AT FINAL
02/12/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999* 1) CLEAN SURFACE UNDER LUG FOR GROUND 250-12 PANEL AND TRANSFER.
2) STRAP SEAL TITLE CONDUIT AT SERVICE 3) LABEL PANELS AND BREAKERS 4) DOUBLE LUG AT JUNCTION CABINET 5) CANNOT USE SHEET METAL SCREWS TO GROUND 250-8 6) FILL ALL UNUSED OPENINGS 7) BOND JUNCTION BOXES 8) ELEC IN CLASSIFIED AREA TO BE MOVED OR INSTALLED TO MEET CODE