Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/26/2001 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000$ | |
| 02/23/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999* | |
| 02/14/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* 1) NO TOOLS AVAILABLE TO ACCESS PANEL AND TRANSFORMER 2) LABEL PANELS 3) NEED MAIN BREAKER TO BE SECURED IN PLACE 384-16(G) *WILL CHECK THESE ITEMS AT FINAL | |
| 02/12/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999* 1) CLEAN SURFACE UNDER LUG FOR GROUND 250-12 PANEL AND TRANSFER. 2) STRAP SEAL TITLE CONDUIT AT SERVICE 3) LABEL PANELS AND BREAKERS 4) DOUBLE LUG AT JUNCTION CABINET 5) CANNOT USE SHEET METAL SCREWS TO GROUND 250-8 6) FILL ALL UNUSED OPENINGS 7) BOND JUNCTION BOXES 8) ELEC IN CLASSIFIED AREA TO BE MOVED OR INSTALLED TO MEET CODE |