Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T00CM04065
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/14/2001 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*1)AS PER VERBAL FROM D. MANN-FLOW PRO 171 N VALVES ARE APPROVED WITH THE STAMP IN THE HANDLE.2)PLUMBING FINAL OK.3)WATTS 2" 009 M20T #155889.4)OK FOR C OF O PENDING ANY OTHER INSPECTIONS AND VERTIFICATION OF CERTIFICATION OF RPBP. 5)MECHANICAL INSPECTOR TO LEAVE UCE. |
|
06/12/2001 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1)FLOW PRO VALVES ARE NOT STAMPED AGA OR CSA IN THE VALVE BODY (ITS STAMPED ON THE HANDLE) THIS IS NOT APPROVED. APPROVED VALVES MUST CARRY THE STAMP ON THE VALVE BODY EITHER AGA OR CSA ONLY. |
|
06/11/2001 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1)PROFLOW 171 N GAS VALVES NOT APPROVED.STAMPED ON HANDLE,NOT IN VALVE BODY AS REQUIRED.2)FINISH STRAPPING GAS PIPE. | |
06/05/2001 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* |