Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/07/2001 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000*1)CLOSET FLANGES OK.PLUMBING INTERMEDIATE COMPLETE.2)GAS PRESSURE TEST OK. | |
| 05/15/2001 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* 1) OK TO TIE IN ABS OVER HEAD 2) CONDENSATE PIPING OK 3) FLOOR DRAINS OK TO COVER 4) I NEED TO SEE CLOSET FLANGES | |
| 05/10/2001 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* 1) ABS DWV OK WATER TEST TO TEN FOOT HEAD OK NOTE: ABS VENT NOT SUPPORTED PROPERLY PLUMBERS TAPE NOT APPROVED STRAP 2) CONDENSATE PIPING NOT COMPLETE 3) 3 HOSE BIBBS OK 4) OK TO COVER WALLS-EXCEPT WHERE CONDENSATE DROPS 5) COPPER PIPE OK PRESSURE TEST OK 6) I NEED TO SEE CONNECTIONS TO FLOOR DRAINS AND JANITORS SINK |