Permit: T00CM04029

Parcel: 118037870

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
11/20/2000 FRAMING Approved IVRS - Inspection 0000*
11/17/2000 FRAMING Denied IVRS - Inspection 0999*/1. COMPLETE BLOCKING AT SHEARWALL #6. 2. SHEARWALL #5 CLIPS STILL NOT NAILED. 3. NO GAS TEST-GUAGE DEFECTIVE AND STUCK ON 11 PSI. 4. CAN NOT VARIFY INSTALLATION OF SMITTY PAN CONDENSATION LINE. BECAUSE OF INSULATION. REMOVE INSULATION IN THIS AREA. 5. PROVIDE SUPPORT TO 4 GANG ELECTRIC BOX IN LIVING ROOM. NOTE: HOUSE WAS INSULATED BEFORE INTERMEDIATE INSPECTIONS.
11/15/2000 FRAMING Denied IVRS - Inspection 0999*/1. NAIL OFF CLIPS AT SHEAR WALL. 2. PROVIDE 1" CLEARANCE FROM COMBUSTIBLES AT ALL FLUES. 3. PROVIDE BOND TO GAS. 4. OVER FRAMING CAN NOT BE INSPECTED NO PLAN. APPROVED SHEETS REQUIRED. MANY OTHER ITEMS NOT READY FOR INSPECTION -SUPER NOT ON SITE TO CHECK HOUSES BEFORE THEY ARE CALLED. SUBJECT TO REFEE AT NEXT INSPECTION.