Permit: T00CM04001

Parcel: 135104440

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
09/27/2000 FRAMING Approved IVRS - Inspection 0000*
09/26/2000 FRAMING Denied IVRS - Inspection 0999*/1. NO PRESSURE TEST ON PEX. PLUMBING NOT COMPLETE. 2. NAIL PROTECT WIRES WITHIN 1 1/4 " OF STUD SURFACES. 3. SCISSOR TRUSS BOTTOM CHORD CANNOT BE WITHIN 1/2" OF NON BEARING WALL. 4. RETURN AIR DUCT RESTRICTED AT HALL BOOT. TOO TIGHT OF BEND RADIUS. 5. PROVIDE POSITIVE SHEAR TRANSFER AT #3 SHEAR WALL WHERE 6" PLUMBING WALL INTERSECTS AND BREAKS DRY WALL SHEAR.