Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/15/2000 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 12/14/2000 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/SMOKE DETECTORS ARE NOT INTER-CONNECTED. |
| 12/13/2000 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/1. GARAGE GFI MISWIRED. 2. TURN FUSES IN A/C DISCONNECT BOX TO READ SIZE 3. UNCAPPED FLUE PIPE. 4. REMOVE COMBUSTABLES FROM FLUE AT ROOF. |