Permit: T00CM03981

Parcel: 140231070


Addresses:

925 E BILBY RD

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
12/14/2000 PLUMBING - GAS PRESSURE TEST Approved PRESSURE TEST OK
PIPING OK
NEED TO SEE FINAL CONNECTIONS
12/13/2000 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0999*
NO ACCESS TO ROOF
NO ACCESS TO ROOM ADACENT TO METER WHERE PIPE ENTERS BLDG
BLACK IRON PIPE NOT ALLOWED UNDERGROUND
UNION MUST BE PRECEDED BY BUILDING SHUT OFF VALVE
ALL APPLIANCE VALVES MUST HAVE AGA OR CSA STAMPED IN BODY
INSTALL UNION ON T&P RELIEF