Permit: T00CM03981

Parcel: 140231070


Addresses:

925 E BILBY RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/05/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
CERTIFICATE OF OCCUPANCY SUBJECT TO OTHER INSPECTOR (S)
01/03/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
MAIN DISCONNECT REQUIRES A NEUTRAL DISCONNECT LINK, MARK ALL DISCONNECTS, SHEET METAL SCREWS NOT ALLOWED FOR BONDING PURPOSE. PLEASE REMOVE APROX. 8" FROM BLOCK WALL FOR PROPER CLEARANCE
MARK A/C BREAKERS
DEVICE EARS CUT, RECEPTACLES SINKING IN, DRYWALL CUT EXCESSIVELY AROUND EARS THAT WERE NOT CUT CAUSING RECEPTACLES TO SINK. REPAIR AND LEAVE ALL FACE PLATES OFF. A RE INSPECTION FEE IS DUE BEFORE THE NEXT INSPECTION