Permit: T00CM03960

Parcel: 133152970

Inspection Status: Denied

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
10/31/2000 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*
10/31/2000 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection 0000*
SOIL WATER TEST OK
P.O.C. OF NEW BLDG DRAIN TO EXSISTING BLDG DRAIN OK
ALL CORRECTIONS HAVE BEEN MADE
OK TO BACKFILL TRENCH
10/30/2000 PLUMBING - ROUGH, SOIL Denied MUST HAVE L-SWEEP FOR LAV WASTE 1/4 BEND CAN BE USED ONLY FOR HORIZONTAL TO VERTICAL DRAINAGE ONLY
RELOCATE 3" MIN OF CLEARANCE
RE TEST SYSTEM