Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/04/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 01/02/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* UPDATE AND INSTALL PANEL SCHEDULE PLUG UNUSED BREAKER SPACES IN PANEL DISCONNECT SWITCH FOR NEW AIR HANDLER IN VIOLATION OF WORKING CLEARANCE DEDICATED SPACE 30" HORIZONTAL 36" IN FRONT NEC 110-26 |