Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/04/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
01/02/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
UPDATE AND INSTALL PANEL SCHEDULE
PLUG UNUSED BREAKER SPACES IN PANEL
DISCONNECT SWITCH FOR NEW AIR HANDLER IN VIOLATION OF WORKING CLEARANCE DEDICATED SPACE
30" HORIZONTAL
36" IN FRONT NEC 110-26