Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 10/03/2000 |
EXT METAL CLIPS/EXT SHEATHING |
|
Approved |
IVRS - Inspection 0000* |
| 09/28/2000 |
EXT METAL CLIPS/EXT SHEATHING |
|
Partial Approval |
|
| 09/26/2000 |
EXT METAL CLIPS/EXT SHEATHING |
|
Not ready for Inspection |
CANCELLED. |
| 09/25/2000 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/1. FRONT #4 SHEARWALLS. SEE PLAN SHEET 5A FOR HOLDOWNS THAT NEED REPLACEMENT 5 IN FRONT 1 AT BACK. 2. JACK TRUSSES FRONT MISSING H2.5S. 3. DETAIL 6/SD3 AT BEARING POST MISSING. MISSING COIL STRAP ALSO STRAPS PER PLAN ARE TO BE INSTALLED EVERY OTHER TRUSS. 4. SIMPSON HTT 22'S NOT INSTALLED. 5. SECOND FLOOR FRONT SWEST SHEARWALL MISSING E. 6. #5 SHEARWALLS AB'S 24" O.C. 7. GIRDER NOT SECURED AS PER PLAN 2ND FLOOR. 8. BLOCKS BETWEEN EVERY OTHER STUB TRUSS. |