Permit: T00CM03915

Parcel: 119180800


Addresses:

3640 S 16TH AV


Inspection Status: Partial Approval

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T00CM03915

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
10/19/2000 PLUMBING - ROUGH, SOIL Partial Approval FLORAL
A. 2 FLOOR SINK AND HAND SINK DWV OK WATER TEST OK VTR OK
B. WATER TO HAND SINK OK
C. OK TO COVER FLOOR AND WALLS
10/11/2000 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*
LAST FLOOR SINK IN MEAT DEPT OK TO COVER
10/10/2000 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*
5 FLOOR SINKS IN FROZEN FOODS OK TO COVER
1 FLOOR SINK IN MEAT DEPT OK TO COVER
10/09/2000 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*
10/06/2000 PLUMBING - ROUGH, SOIL Partial Approval FROZEN FOODS EAST SIDE 3 FLOOR SINKS
WATER TEST OK
CONNECTIONS OK
OK TO COVER MEAT SECTION CENTER 3
WATER TEST OK CONNECTIONS OK
OK TO COVER
10/05/2000 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*
1. FINAL FLOOR SINK IN PRODUCE OK
EAST MOST FLOOR SINK IN LIQUOR OK
2 FLOOR SINKS N SIDE PRUDUCE OK
10/04/2000 PLUMBING - ROUGH, SOIL Partial Approval 10/04/00 3 FLOOR SINKS IN PRODUCE OK STILL NEED TO INSPECT ONE
2. WEST SIDE FROZEN FOODS MOVED FLOOR SINKS OK
OK TO COVER
09/15/2000 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*
CONDENSING UNIT FLOOR SINK CHANGED CHANGE IS OK
WATER TEST OK
OK TO COVER
09/13/2000 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*
09/13/2000 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*
BATHROOM DRAIN TIE IN OK
FLOOR SINK AT CONDENSING UNIT OK
A. NEED TO SEE TIE IN BEYOND SLAB
B. NEED TO SEE VENT RUN BEYOND SLAB
OK TO COVER BOTH AREAS
09/12/2000 PLUMBING - ROUGH, SOIL Denied FURNCO COUPLING NOT APPROVED INSIDE UNDERSLAB MUST USE SPECIALTY COUPLING MISSION
WATER TEST OK RISERS ONLY MUST RETEST TO 42"
OK TO COVER EVERYTHING BUT TIE IN TO EXISTING
09/08/2000 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection 0000*
NOTE READY AT THIS TIME