Permit: T00CM03905


Addresses:

3159 E PRINCE RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/07/2000 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
APPROVAL BASED ON FAXED INFORMATION FROM BRIAN ROBERTS (CRICKET COMMUNICATIONS) APPROVED OK TO CLEAR ECO
12/06/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0245*
NOTE DID NOT COMPLY WITH PREVIOUS WRITE UP
12/01/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0245*
GROUND GRID SYSTEM CONDUCTOR ON TOP OF CONCRETE SLAB IS A TRIP HAZARD, ALSO VIOLATES WORKING SPACE IN FRONT OF HINGED DOOR OF CONTROL CABINATE 110-26 NEC CONTRACTOR NOT ON SITE