Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/17/2000 | ELECTRIC - INTERMEDIATE | Approved | ||
| 09/27/2000 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* CONNECT GROUND BOND CONDUCTOR T 1 1/2" RIGID NIPPLE BOND BUSHING, 250-94 N.E.C. BOND SCREW ON NEUTRAL BUSS IN DISCONNECT SWITCH SHOULD BE GREEN TO I.D. AS BOND SCREW IN PLACE OF BOND JUMPER, 250-28 B N.E.C. |