Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 03/08/2001 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* OVER HEAD WATER DISTRIBUTION IS TYPE (M) HARD COPPER AND SPECS CALL FOR TYPE (L) WILL REQUIRE A LETTER FROM ARCHITECT STATING HE WILL ACCEPT TYPE (M) COPPER PRIOR TO FINAL |
| 03/07/2001 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999* LOCKED NO ACCESS |
| 02/21/2001 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999* 1) RE-VENT FOR RESTROOM PLUM. MUST BE 42" A.F.F. 2) APPROVED DRAWING SHOWS TYPE L COPPER ABOVE SLAB SEE PLUM. NOTE #18 ON APPROVED PLAN 3) CLOSET RINGS NOT INSTALLED |