Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/31/2001 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection 0000* ALL CORRECTIONS MDE OK OK TO BACKFILL |
|
| 01/29/2001 | PLUMBING - ROUGH, SOIL | Denied | CAN NOT HAVE ANY THREADED FITTINGS BELOW CONCRETE SEE SECTION 316.1.5 94 UPC GREASE TRAP OUTLET HAS OBSTRUCTION OF FLOW THIS DRAIN LINE MUST BE 3" SEC SECTION 311.5 94 UPC CAN NOT WEST VENT 3" GREASE TRAP INTO 2" VERTICAL DRAIN AT FLOOR SINK SEE SECTION 706.2 94 UPC. NOT TO PLAN CAN ONLY FLAT VENT FIXTURES DUE TO STRUCTURE CONDITIONS, FLOOR SINK FOR SODA MACHINE MUST BE A CONVENTIONAL ROUGH AS PER PLAN SEE SECTION 905.3 WASTE LINE FOR FLOOR SINK AT WEST WALL EXCEEDS 135 DEGREE SEE SECTION 707.5 94 UPC TRAP ARM FOR FLOOR SINK AT WEST WALL HAS MORE THAN 1-90 DEGREE SEE SECTION 1002.3 94 UPC RE TEST SYSTEM |