Permit: T00CM03878

Parcel: 125170380


Addresses:

3827 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T00CM03878

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
04/23/2001 ELECTRIC - ABOVE CEILING Approved
04/17/2001 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0999*1. STRAP & SUPPORT CABLE IN CEILING 2. PANEL SCHEDULE IN 200 A PANEL DOES NOT REFLECT PLAN THERE IS A NEW 30A 3 PHASE AC, WALKIN COOLERIS 2 PHASE VERSE 1 P 3. WATER EHATER NOT IN OR CONNECTED. 4. CIRCUIT A-16 MISSING 5. BREAD OVEN MISSING I O SEAL BACK JUNCTION BOX 6. NOTE 11 ON SHEET E-1 STATES ALL APPLIANCES TO HAVE DISCONNECTS PER NEC 99 # 422-31(B) 7. APPEARS THE LOAD CALCULATIONS HAVE CHANGED ENOUGH TO WARRENT CORRECTION TO POLAN 8. COVER TOP OF DISCONNECT TO AC SWITCH 9. COMPRESSOR ON ROOF TO BE PERMANENTLY MOUNTED 10 REDO TERMINATIONS ON REPLACED AC WIRES LINE SIDE - BURNT
04/13/2001 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0935*HAS NOT PAID RE-FEE.
04/12/2001 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0935*
04/11/2001 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245* 1) PLUG OPEN KO'S IN J BOXES 2) FLEX CONDUIT EAST WALL MUST BE SUPPORTED PER 350-18 NEC 3) CEILING BOX'S (GRID) FOR HANGING LAMPS MUST BE SUPPORTED TO STRUCTURE 300.4-11 NEC