Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T00CM03878
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/23/2001 | ELECTRIC - ABOVE CEILING | Approved | ||
04/17/2001 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0999*1. STRAP & SUPPORT CABLE IN CEILING 2. PANEL SCHEDULE IN 200 A PANEL DOES NOT REFLECT PLAN THERE IS A NEW 30A 3 PHASE AC, WALKIN COOLERIS 2 PHASE VERSE 1 P 3. WATER EHATER NOT IN OR CONNECTED. 4. CIRCUIT A-16 MISSING 5. BREAD OVEN MISSING I O SEAL BACK JUNCTION BOX 6. NOTE 11 ON SHEET E-1 STATES ALL APPLIANCES TO HAVE DISCONNECTS PER NEC 99 # 422-31(B) 7. APPEARS THE LOAD CALCULATIONS HAVE CHANGED ENOUGH TO WARRENT CORRECTION TO POLAN 8. COVER TOP OF DISCONNECT TO AC SWITCH 9. COMPRESSOR ON ROOF TO BE PERMANENTLY MOUNTED 10 REDO TERMINATIONS ON REPLACED AC WIRES LINE SIDE - BURNT | |
04/13/2001 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0935*HAS NOT PAID RE-FEE. | |
04/12/2001 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0935* | |
04/11/2001 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245* 1) PLUG OPEN KO'S IN J BOXES 2) FLEX CONDUIT EAST WALL MUST BE SUPPORTED PER 350-18 NEC 3) CEILING BOX'S (GRID) FOR HANGING LAMPS MUST BE SUPPORTED TO STRUCTURE 300.4-11 NEC |