Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/19/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* OK ELECTRICAL FINAL ECO |
|
| 01/18/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* DENIED LOCKED A RE INSPECTION FEE IS DUE BEFORE THE NEXT INSPECTION |
|
| 12/28/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* MAIN BREAKER PER PLANS NEED TO BE 22 KAIC AT INTERIOR PANEL |
|
| 12/26/2000 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* NEED WORK DONE AS PER CITY APPROVED PLANS (EXISTING OR REVISED) |
|
| 12/20/2000 | ELECTRIC - FINAL | Denied | WIRE PANEL BOARD PER PLAN (W/22KAIC) MAIN BREAKER) USE CORRECT LISTED GROUND SCREW |
|
| 12/15/2000 | ELECTRIC - FINAL | Not ready for Inspection | NOT READY NEED RE-FEE PAID 1ST | |
| 12/14/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999$ NO GROUND SCREW IN DISCONNECTS RISER NEEDS GROUNDING BUSHING AND BOND JUMPER TIGHTEN LOCK NUTS MUST INTER TO VERIFY BREAKER |
|
| 12/11/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* STRAP GORUND WIRE ENCLOUSRE FOR FIRMLY TO WALL NEED TO INSTALL BOND SCREWS INTO NEUTRAL BAR AN BOTH SERVICE DISCONNECTS NEED TO INSTALL RISER NEED TO ENTER IF MAIN BREAKER OMITTED AT SUB PANEL WILL NEED TO FAX VERIFICATION OF RE-CALCUATION FROM 35 KAIC TO 10 KAIC PLEASE FAX TO RM |
|
| 12/06/2000 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
| 11/30/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* NEED GROUNDING ELECTRODE SYSTEM FOR BOTH MAIN DISCONNECT AND GENERATOR DISCONNECT TRANSFER SWITCH NOT A SOLID NEUTRAL NEED 22 K 10/L SERVICE RATING PLEASE HIGHLIGHT WHERE THIS IS ACCEPT |
|
| 11/28/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0925* NO PLANS OR PERMIT ON SITE 925 |