Permit: T00CM03872

Parcel: 13822016B


Addresses:

980 W LOS REALES RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/19/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
OK ELECTRICAL FINAL ECO
01/18/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
DENIED LOCKED A RE INSPECTION FEE IS DUE BEFORE THE NEXT INSPECTION
12/28/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
MAIN BREAKER PER PLANS NEED TO BE 22 KAIC AT INTERIOR PANEL
12/26/2000 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
NEED WORK DONE AS PER CITY APPROVED PLANS (EXISTING OR REVISED)
12/20/2000 ELECTRIC - FINAL Denied WIRE PANEL BOARD PER PLAN (W/22KAIC) MAIN BREAKER)
USE CORRECT LISTED GROUND SCREW
12/15/2000 ELECTRIC - FINAL Not ready for Inspection NOT READY NEED RE-FEE PAID 1ST
12/14/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999$
NO GROUND SCREW IN DISCONNECTS
RISER NEEDS GROUNDING BUSHING AND BOND JUMPER TIGHTEN LOCK NUTS
MUST INTER TO VERIFY BREAKER
12/11/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
STRAP GORUND WIRE ENCLOUSRE FOR FIRMLY TO WALL
NEED TO INSTALL BOND SCREWS INTO NEUTRAL BAR AN BOTH SERVICE DISCONNECTS
NEED TO INSTALL RISER
NEED TO ENTER
IF MAIN BREAKER OMITTED AT SUB PANEL WILL
NEED TO FAX VERIFICATION OF RE-CALCUATION FROM 35 KAIC TO 10 KAIC PLEASE FAX TO RM
12/06/2000 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
11/30/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
NEED GROUNDING ELECTRODE SYSTEM
FOR BOTH MAIN DISCONNECT
AND GENERATOR DISCONNECT TRANSFER SWITCH
NOT A SOLID NEUTRAL
NEED 22 K 10/L SERVICE RATING PLEASE HIGHLIGHT WHERE THIS IS ACCEPT
11/28/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0925*
NO PLANS OR PERMIT ON SITE 925