Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T00CM03871
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/12/2001 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* CORRECTIONS OK CONTRACTOR AERO STAR ELEC. LIC# 1112747 | |
| 02/07/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0935* HAS NOT COMPLIED WITH PREVIOUS WRITE UP AS NOTED, OUTSIDE LIGHT PANCAKE BOX, HANDY BOX UNDER KITCHEN WINDOW. ALSO ROMEX WIRING CANNOT BE INSTALLED WITHOUT PROTECTION AS NOTED IN ART 300-4D N.E.C. PLEASE PAY RE INSPECTION FEE PRIOR TO NEXT INSPECTION |
|
| 02/01/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245* NO ACCESS DOORS LOCKED NO MESSAGE RE FEE WILL BE ASSESED NEXT INSPECTION IF NOT IN COMPLAINACE WITH PREVIOUS WRITE-UP OR IF NO ACCESS |
|
| 01/29/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245* NOTES: HANDY BOXES OVER FILLED, INSTALL DEEPER BOX, 370-16 NEC, (WINDOW WEST KITCHEN WALL) PLASTIC PUSH IN BUSHINGS NOT APPROVED ON METAL BOXES WITH ROMEX, MUST BE CLAMP TYPE TO SECURE WIRING OR CABLE TO BOX 370-17 B.C. WHERE CONDUIT IS USED TO PROTECT CABLE A FITTING MUST BE PROVIDED AT ENDS OF CONDUIT. 300-15 A- THRU -C PLEASE LEAVE NAME AND PHONE NUMBER OF LICENSED CONTRACTOR C-11 ELECTRICAL |