Permit: T00CM03871

Parcel: 12203050B


Addresses:

1932 N MADELYN AV


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T00CM03871

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
02/12/2001 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000* CORRECTIONS OK CONTRACTOR AERO STAR ELEC. LIC# 1112747
02/07/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0935*
HAS NOT COMPLIED WITH PREVIOUS WRITE UP AS NOTED, OUTSIDE LIGHT PANCAKE BOX, HANDY BOX UNDER KITCHEN WINDOW.
ALSO ROMEX WIRING CANNOT BE INSTALLED WITHOUT PROTECTION AS NOTED IN ART 300-4D N.E.C.
PLEASE PAY RE INSPECTION FEE PRIOR TO NEXT INSPECTION
02/01/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*
NO ACCESS DOORS LOCKED
NO MESSAGE
RE FEE WILL BE ASSESED NEXT INSPECTION IF NOT IN COMPLAINACE WITH PREVIOUS WRITE-UP OR IF NO ACCESS
01/29/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*
NOTES: HANDY BOXES OVER FILLED, INSTALL DEEPER BOX, 370-16 NEC, (WINDOW WEST KITCHEN WALL)
PLASTIC PUSH IN BUSHINGS NOT APPROVED ON METAL BOXES WITH ROMEX, MUST BE CLAMP TYPE TO SECURE WIRING OR CABLE TO BOX 370-17 B.C.
WHERE CONDUIT IS USED TO PROTECT CABLE A FITTING MUST BE PROVIDED AT ENDS OF CONDUIT. 300-15 A- THRU -C
PLEASE LEAVE NAME AND PHONE NUMBER OF LICENSED CONTRACTOR C-11 ELECTRICAL