Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 10/02/2000 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 09/28/2000 |
FRAMING |
|
Denied |
1. SHEARWALL #3 AT GARAGE SHOULD BE FRAMED 16" O.C. ALL STUDS NAILED PER SCHEDULE. 2. SHEARWALL ALSO NEEDS A DOUBLE TOP PLATE AS PER PLAN. 3. HD2A WITH 5/8 EXP. BOLTS NOT INSTALLED AS PER PLAN ALTERNATIVE HOLDOWNS SHALL BE INSTALLED PER MANF. SPECS DOUBLE STUDS FROM SOLE PLATE TO DOUBLE TOP PLATE. 4. PROVIDE VERTICAL DEFECTION FOR SCISSOR TRUSS. 5. SEAL PENETRATIONS OVER 1/4 INCH AT SOLE PLATE TO WEEP SCREED. 6. ISOLATE PLENUM TO BATH TUB. 7. PROTECT ABS GARAGE BACK WALL. 8. FHA STRAP OVER BORED DBL TOP PLATE WITH LESS THAN 5/8 MEET FROM EDGE. |