Permit: T00CM03844

Parcel: 137117890


Addresses:

5653 S BALLANTRY DR

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
10/02/2000 FRAMING Approved IVRS - Inspection 0000*
09/28/2000 FRAMING Denied 1. SHEARWALL #3 AT GARAGE SHOULD BE FRAMED 16" O.C. ALL STUDS NAILED PER SCHEDULE. 2. SHEARWALL ALSO NEEDS A DOUBLE TOP PLATE AS PER PLAN. 3. HD2A WITH 5/8 EXP. BOLTS NOT INSTALLED AS PER PLAN ALTERNATIVE HOLDOWNS SHALL BE INSTALLED PER MANF. SPECS DOUBLE STUDS FROM SOLE PLATE TO DOUBLE TOP PLATE. 4. PROVIDE VERTICAL DEFECTION FOR SCISSOR TRUSS. 5. SEAL PENETRATIONS OVER 1/4 INCH AT SOLE PLATE TO WEEP SCREED. 6. ISOLATE PLENUM TO BATH TUB. 7. PROTECT ABS GARAGE BACK WALL. 8. FHA STRAP OVER BORED DBL TOP PLATE WITH LESS THAN 5/8 MEET FROM EDGE.