Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/26/2000 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* | |
| 09/20/2000 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* ELECT. HI VOLTAGE WIRING TO UNIT IS OK FOR HEAT PUMP ONLY. NOT LARGE ENOUGH FOR COMBINED HEAT PUMP AND AUX. HT. STRIPS TOGETHER. NEED 1 LARGER CIRCUIT, OR 2. REMOVE AUX HEIGHT STRIP |
|
| 09/20/2000 | MECHANICAL - FINAL | Denied | RE-FEE DUE READ MECHANICAL NOTES ITEM # 3&# B PROBLEM PANEL TO ROOF TOP HEAT PUMP 1. GO AMP 3 PHASE CIRCUIT UNIT AS SUPPLIED REQUIRES A LARGE CIRCUIT FOR HEAT PUMP PLUS AUX HT. STRIPS AS SPEC'D SEE WRITE UP FROM 09/19/00 ELECT NEEDS TO BE ADDRESSED! |