Permit: T00CM03836

Parcel: 14042075B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/21/2000 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
SEE MECH WRITE UP ON DISCON FOR UNIT ON ROOF
CONDUIT ENTRY TO 100 AMP SW AT BOTTOM NOW
REQUIRED TO HAVE A BOND BUSHING AND JUMPER TO CAN (NEW IN 99 NEC 250-AT SERVICES)
REAR ROOM MISSING 3 CEILING FIXTURES OK ON THIS RESOLVERS OK TO CLEAR ECO
09/20/2000 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*