Permit: T00CM03834

Parcel: 118037810

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
12/11/2000 FRAMING Approved IVRS - Inspection 0000*
12/08/2000 FRAMING Denied 1. BLOCK MECHANICAL KNOCK OUTS MINIMUM 3 SIDES. 2. GFCI BRANCH CIRCUIT FOR BATHROOM RECEPS CAN ONLY SERVE RECEP. OUTLETS. SEE NEC. 210 (11) (C) (3). 3. PLATFORM MECHANICAL NOT INSTALLED AS PER PLAN 3 4 X 6 HEADER BEAMS NOT INSTALLED PROVIDE POST TO BEAM CONNECTION AT PLATFORM 4 X 10 BEAM. 4. INSTALL ANCHOR BOLTS AT SHEARWALL ENDS AS PER PLAN. 5. TRUSSES NOT MISSING H2.5 AT PLATFORM LOCATION. 6. PROTECT ELECTRICAL ROMEX WITHIN 1 1/4 OF STUD EDGE THRU OUT. 7. SEAL EXTERIOR WEATHER BARRIER AT INSIDE PER UBC 1402.1.