Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T00CM03826

Parcel: 13621127A


Addresses:

7322 E 42ND ST

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
05/04/2001 FRAMING Approved IVRS - Inspection 0000*
01/23/2001 FRAMING Not ready for Inspection IVRS - Inspection 0000*/1. BEARING WALL 15'8" FROM FRONT NOT INSTALLED (2 X 8 18'4" FLAN 17'9" FIELD.) 2. THE TOP OF WALL N/SOUTH TO ROOF RAFTERS. 3. H20 LINE TO BE 12" BELOW GRADE, FEMALE FITTING TO BE PLASTIC. 4. ISOLATE COPPER FROM STEEL. 5. MISSING P-TRAP AND VENT AT WASHER 6. NOT USING 98 FITTINGS CORRECTLY. 7. 2" SEWER TIE IN DONE INCORRECTLY. 8. H20 BOND OR GROUND DISCONNECTED CAN'T GET ELECT. SERV. PANEL OPEN. 10. NO PRIMER USED ON P.V.C. H20 LINE. 11. NEED MIN. 3 STUDS PER CORNER 12. HOW MANY CIRCUITS ARE YOU INSTALLING? 13. MOVE CLOSET LIGHT FARTHER NORTH. 14. H20 HEAT COLD SHOULD BE ON THE RIGHT SIDE. 15. TIGHTEN ALL ANCHOR BOLTS.