Permit: T00CM03793

Parcel: 141085210

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
08/14/2001 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
03/14/2001 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0240* 1) PLEASE REFER TO NEC ART. 300-11 THE SUPPORT WIRES TIED TO FIXTURES (SIZEMIC WIRES) AND THE GRID SUPPORT CONDUIT AND BOXES. THE WIRES WHICH SUPPORT CONDUIT AND J BOXES MUST BE SEPERATE FROM GRID AND FIXURE WIRES AND MUST BE FASTENED AT BOTH ENDS. BOTTOM END TO GRID T BAR MAIN RUNNERS WHEREVER POSSIBLE. CORRECT AND RE CALL