Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T00CM03760
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/09/2000 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection 0000* | |
11/03/2000 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection 0000*/1. SECOND ROOF TRUSS FROM EAST WALL BROKEN PROVIDE COT AND ENGINEER REPAIR DOC. | |
11/01/2000 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection 0950*/1. 3/SD4 NOT COMPLIED WITH AND TRUSS MISSING (2 EACH). 2. CLIP STUDS TOP AND BOTTOM. 3. POST AND BEAM CONNECTIONS MUST COMPLY WITH 1/3D. 4. PROVIDE DETAIL OF POST TO BOTTOM PLATE CONNECTION. 5. DRAG STRUTS MISSING AT GARAGE SEE 15/SD3. 6. INCORRECT HANGER ON 4 X 12 GLB ABOVE ENTRY. 7. WALL BRACING MISSING. 8. PROVIDE ANCHOR BOLTS (REDHEADS) LENGTH REQUIREMENTS FOR EXTERIOR BOTTOM PLATES AND SHEAR WALLS PRESENTLY USING 4 1/4" WITH 2" EMBEDMENT. 9. TRUSS'S K-02 IN WRONG LOCATION AND NOT PROPERLY BEARING. |