Permit: T00CM03760

Parcel: 110045680

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T00CM03760

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
11/09/2000 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection 0000*
11/03/2000 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection 0000*/1. SECOND ROOF TRUSS FROM EAST WALL BROKEN PROVIDE COT AND ENGINEER REPAIR DOC.
11/01/2000 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0950*/1. 3/SD4 NOT COMPLIED WITH AND TRUSS MISSING (2 EACH). 2. CLIP STUDS TOP AND BOTTOM. 3. POST AND BEAM CONNECTIONS MUST COMPLY WITH 1/3D. 4. PROVIDE DETAIL OF POST TO BOTTOM PLATE CONNECTION. 5. DRAG STRUTS MISSING AT GARAGE SEE 15/SD3. 6. INCORRECT HANGER ON 4 X 12 GLB ABOVE ENTRY. 7. WALL BRACING MISSING. 8. PROVIDE ANCHOR BOLTS (REDHEADS) LENGTH REQUIREMENTS FOR EXTERIOR BOTTOM PLATES AND SHEAR WALLS PRESENTLY USING 4 1/4" WITH 2" EMBEDMENT. 9. TRUSS'S K-02 IN WRONG LOCATION AND NOT PROPERLY BEARING.