Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/26/2001 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 11/20/2001 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*PLEASE SEC TABLE 6-1 REMOVE ATMOSPHERIC VB. YOU HAVE A VALUE DOWN STREAM. A MIN STANDARD FOR THIS TYPE OF INSTALL WOULD BE PRESSURE VB. MIN 12" ABOVE ALL DOWN STREAM PIPING OR RIM. FOUNTAIN IS RIM. |
| 11/14/2001 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*NEW 1 1/4 SITE WATER TEST OK WILL REQUIRE TEST ON BACKFLOW DEVICE. ALSO A BACKFLOW REQUIRED ON FOUNTAIN WILL SEC THIS AT FINAL PROVIDE LETTER ON NEW SITE WATER. |