Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T00CM03755
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/06/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
11/29/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*OK TO CLEAR POWER. 1.) NEED TO SEE AFTER CROSS OVER. | |
11/27/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0935*1.) BONDING JUMPERS TO BE SIZED PER CODE 250-102 & TABLE 250-66 USE CORRECT SIZE LUG FOR CONDUCTORS A REFEE HAS BEEN ASSESSED. | |
11/26/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) BUILDING JUMPERS TO BE SIZED PER CODE 250-102 TABLE 250-66. 2.) BOND METER ENCLOSURE. 3.) GROUNDING IN WATER HEATER DISCONNECT TO BE CORRECTED CANNOT STACK LUGS, NEED TO BE ON A CLEANED SURFACE NOT FLAT WASHER. 4.) SEAL UNUSED OPENINGS. | |
11/20/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* |