Permit: T00CM03755

Parcel: 11706073A


Addresses:

401 E 9TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/06/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
11/29/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*OK TO CLEAR POWER. 1.) NEED TO SEE AFTER CROSS OVER.
11/27/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0935*1.) BONDING JUMPERS TO BE SIZED PER CODE 250-102 & TABLE 250-66 USE CORRECT SIZE LUG FOR CONDUCTORS A REFEE HAS BEEN ASSESSED.
11/26/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) BUILDING JUMPERS TO BE SIZED PER CODE 250-102 TABLE 250-66. 2.) BOND METER ENCLOSURE. 3.) GROUNDING IN WATER HEATER DISCONNECT TO BE CORRECTED CANNOT STACK LUGS, NEED TO BE ON A CLEANED SURFACE NOT FLAT WASHER. 4.) SEAL UNUSED OPENINGS.
11/20/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*