Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/06/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 11/29/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*OK TO CLEAR POWER. 1.) NEED TO SEE AFTER CROSS OVER. |
| 11/27/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0935*1.) BONDING JUMPERS TO BE SIZED PER CODE 250-102 & TABLE 250-66 USE CORRECT SIZE LUG FOR CONDUCTORS A REFEE HAS BEEN ASSESSED. |
| 11/26/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) BUILDING JUMPERS TO BE SIZED PER CODE 250-102 TABLE 250-66. 2.) BOND METER ENCLOSURE. 3.) GROUNDING IN WATER HEATER DISCONNECT TO BE CORRECTED CANNOT STACK LUGS, NEED TO BE ON A CLEANED SURFACE NOT FLAT WASHER. 4.) SEAL UNUSED OPENINGS. |
| 11/20/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |