Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
Permit Number - T00CM03755
Inspection Description - ELECTRIC - SERVICE RELOCATION
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/10/2001 | ELECTRIC - SERVICE RELOCATION | Approved | ||
08/28/2001 | ELECTRIC - SERVICE RELOCATION | Partial Approval | IVRS - Inspection 0000* | |
08/26/2001 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection 0999*1.) BOND ENCLOUSER GUTTER 2.) NEED BONDING DEVICE ON 4" NIPPLE 3.) DOUBLE LUGGING ON GROUND 4.) LOOSE CONDUIT FITTING 5.) PLEASE PROVIDE INFORMATION REGRADING LISTING USE OF COMPRESSION CONNECTOR ON MC CONDUIT. | |
08/22/2001 | ELECTRIC - SERVICE RELOCATION | Not ready for Inspection | IVRS - Inspection 0000*COUTESY CALL TO ANSWER QUESTIONS. |