Permit: T00CM03755

Parcel: 11706073A


Addresses:

401 E 9TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE RELOCATION

Date Description Inspector Results Comments
12/10/2001 ELECTRIC - SERVICE RELOCATION Approved
08/28/2001 ELECTRIC - SERVICE RELOCATION Partial Approval IVRS - Inspection 0000*
08/26/2001 ELECTRIC - SERVICE RELOCATION Denied IVRS - Inspection 0999*1.) BOND ENCLOUSER GUTTER 2.) NEED BONDING DEVICE ON 4" NIPPLE 3.) DOUBLE LUGGING ON GROUND 4.) LOOSE CONDUIT FITTING 5.) PLEASE PROVIDE INFORMATION REGRADING LISTING USE OF COMPRESSION CONNECTOR ON MC CONDUIT.
08/22/2001 ELECTRIC - SERVICE RELOCATION Not ready for Inspection IVRS - Inspection 0000*COUTESY CALL TO ANSWER QUESTIONS.