Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date |
Description |
Inspector |
Results |
Comments |
| 12/10/2001 |
ELECTRIC - UFER |
|
Approved |
|
| 11/20/2001 |
ELECTRIC - UFER |
|
Partial Approval |
IVRS - Inspection 0000*1.) GROUNDING ELECTRODE TO BE BONDED TO GROUNDED CONDUCTOR 250025 2.) BONDING JUMPERS TO BE SIZE PER CODE 250-102. 3.) BOND METER ENCLOUSER 4.) NEED ALL FIXTURES INSTALLED. 5.) NEED GAS & WATER BOND. 6.) SUPPER IS IN A WORKING CLEARENCE VIOLATION OK PANEL "A" OK 2 GROUNDROD. |