Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
Permit Number - T00CM03755
Inspection Description - ELECTRIC - UFER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/10/2001 | ELECTRIC - UFER | Approved | ||
11/20/2001 | ELECTRIC - UFER | Partial Approval | IVRS - Inspection 0000*1.) GROUNDING ELECTRODE TO BE BONDED TO GROUNDED CONDUCTOR 250025 2.) BONDING JUMPERS TO BE SIZE PER CODE 250-102. 3.) BOND METER ENCLOUSER 4.) NEED ALL FIXTURES INSTALLED. 5.) NEED GAS & WATER BOND. 6.) SUPPER IS IN A WORKING CLEARENCE VIOLATION OK PANEL "A" OK 2 GROUNDROD. |