Permit: T00CM03738

Parcel: 137336800


Addresses:

6250 S MANUS PL

Inspection Status: Partial Approval

Inspection History: FRAMING

Date Description Inspector Results Comments
10/10/2000 FRAMING Partial Approval IVRS - Inspection 0000*/1. ENGINEERS FIX NOT APPROVED BY CITY OF TUCSON. KING STUD NEEDS REMOVED TO HAVE CONTINOUS SHEARWALL AS PER FIX. PROCEED AT OWN RISK PENDING CITY APPROVAL. 2. PROVIDE APPROVED TRUSS CALC'S 3. REGISTERS NOT INSTALLED IN CLOSET AS PER PLAN PROVIDE OR OMIT NEED APPROVAL FROM PLANS.
10/09/2000 FRAMING Denied IVRS - Inspection 0999*/NO PLANS OR PERMIT ON SITE.
10/04/2000 FRAMING Partial Approval 1. THE ENGINEERS FIX DOES NOT APPLY TO THIS SHEARWALL IT APPLYS FOR OVER BORED ALSO ANY FIX PROVIDED MUST BE APPROVED BY CITY PLAN CHECK. 2. COMBUSTIBLE MATERIALS ARE IN DIRECT CONTACT WITH FIRE PLACE FLUE PROVIDE THE REQUIRED CLEARANCE SECURE FLUE. 3. CONDENSATE OVER FLOW LINE HAS A SAG IN PROVIDE POSITIVE FLOW SECURE 4' O.C.
10/02/2000 FRAMING Partial Approval IVRS - Inspection 0000*/PROVIDE ENG. FIX FOR SH. WALL AT FIREPLACE 3/4" GAS LINE NOT INSTALLED FOR 'O' CLEARANCE FIREPLACE PER PLAN COMBUSTABLE MAT. AT FURNACE FLUE PROVIDE 1" CLEARANCE UNABLE TO APPROVE INTERMEDIATE MECH. UNTIL ROOF IS DRIED IN.