Permit: T00CM03706

Parcel: 122152710


Addresses:

2185 N NORTHWAY AV

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
10/31/2000 FRAMING Approved IVRS - Inspection 0000*
10/25/2000 FRAMING Partial Approval IVRS - Inspection 0000*/1. REVISE SITE PLAN TO SHOW DISTANCE TO SOUTH PROPERTY LINE AS ONLY 1 FT. 6" AND HAVE APPROVED BY CITY OF TUCSON. 2. INSTALL U26 HANGERS ON ALL RAFTERS AND HEADERS FOR SKYLIGHT. 3. OK TO INUSLATE AND DRYWALL ALL BUT SKY LIGHT AREA.
10/18/2000 FRAMING Denied 1. PROVIDE PROOF OF LOCATION OF SOUTH PROPERTY LINE. PLAN CALLS FOR FLUE FEED. FENCE IS LOCATED ONLY 20" FROM SOUTH WALL. IF PROPERTY LINE IS NOT 5' AWAY REVISE PLAN. 2. PROVIDE PROOF OF GAS LINE PRESSURE TEST OR PROVIDE NEW TEST PER CODE. 3. ROOF NOT PROPERLY SUPPORTED COMPLETE BOND BEAM. 4. PROVIDE FRAMED ACCESS BOX TO ABOVE CEILING JUNCTION BOX. 5. INSTALL ELECT CONDUIT FOR COOLER. 6. SKYLIGHT NOT IN. 7. PARAPET WALL NOT BUILT. 8. BATHROOM GFCI MUST BE ON DEDICATED CIRCUIT. 9. NAIL PROTCT PEX WITHIN 1 1/2" OF STUD SURFACE.
10/12/2000 FRAMING Denied IVRS - Inspection 0999*
10/11/2000 FRAMING Not ready for Inspection IVRS - Inspection 0000*/NO PLANS OR PAPER WORK LEFT ON SITE.