Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 10/31/2000 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 10/25/2000 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/1. REVISE SITE PLAN TO SHOW DISTANCE TO SOUTH PROPERTY LINE AS ONLY 1 FT. 6" AND HAVE APPROVED BY CITY OF TUCSON. 2. INSTALL U26 HANGERS ON ALL RAFTERS AND HEADERS FOR SKYLIGHT. 3. OK TO INUSLATE AND DRYWALL ALL BUT SKY LIGHT AREA. |
| 10/18/2000 |
FRAMING |
|
Denied |
1. PROVIDE PROOF OF LOCATION OF SOUTH PROPERTY LINE. PLAN CALLS FOR FLUE FEED. FENCE IS LOCATED ONLY 20" FROM SOUTH WALL. IF PROPERTY LINE IS NOT 5' AWAY REVISE PLAN. 2. PROVIDE PROOF OF GAS LINE PRESSURE TEST OR PROVIDE NEW TEST PER CODE. 3. ROOF NOT PROPERLY SUPPORTED COMPLETE BOND BEAM. 4. PROVIDE FRAMED ACCESS BOX TO ABOVE CEILING JUNCTION BOX. 5. INSTALL ELECT CONDUIT FOR COOLER. 6. SKYLIGHT NOT IN. 7. PARAPET WALL NOT BUILT. 8. BATHROOM GFCI MUST BE ON DEDICATED CIRCUIT. 9. NAIL PROTCT PEX WITHIN 1 1/2" OF STUD SURFACE. |
| 10/12/2000 |
FRAMING |
|
Denied |
IVRS - Inspection 0999* |
| 10/11/2000 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000*/NO PLANS OR PAPER WORK LEFT ON SITE. |