Inspection History: REINFORCED MASONRY PRE-GROUT

Date Description Inspector Results Comments
10/12/2000 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection 0000*/1. ROOM LAYOUT AND SIZES ARE NOT PER PLAN. BUILD TO PLAN OR REVISE TO PLAN TO AS BUILT AND HAVE APPROVED. 2. 1/2" ROUND BOXES INSTALLED IN CEILING ARE NOT APPROVED FOR FANS--INSTALL APPROVED BOXES. 3. GROUND ALL METAL ELECTRIC BOXES. 4. PROVIDE GROUND WIRES FOR LIGHT SWITCHES. 5. MAKE UP ALL GROUND WIRES IN BOXES. 6. PLAN CALLS FOR 4040 WINDOW 6040 INSTALLED REVISE PLAN. 7. JUNCTION BOXES CANNOT BE ENCLOSED ABOVE CEILING EXTEND FOR ACCESS OR PROVIDE ACCESS PANEL. 8. PROVIDE NAIL PROTECTION FOR WIRES WITHIN 1 1/4" OF STUD SURFACE.
10/11/2000 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection 0000*
09/21/2000 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*/4 FT LIFT OK.