Permit: T00CM03694


Addresses:

210 E BROADWAY BL

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
07/09/2001 BUILDING - FINAL Approved
06/22/2001 BUILDING - FINAL Approved
06/13/2001 BUILDING - FINAL Partial Approval IVRS - Inspection 0000*PROVIDE APROVALS ON MECHANICAL AND SIGN INSPECTIONS.
06/05/2001 BUILDING - FINAL Not ready for Inspection IVRS - Inspection 0000*1)TRUSS BRACES DON'T APEAR TO BE 6"X18"X18GA. SUBMIT "AS BUILT"
DRAWINGS TO THE PROJECT ENGINEER FOR REVIEW.SPECIFTY GAUGE OF MATERIAL USED.2)IS DRAWING SK-7 AN ACCEPTIBLE OPTION IN LIEU OF,
NOT IN ADDITION TO, NOTE 2 ON SK-IR?
02/13/2001 BUILDING - FINAL Not ready for Inspection IVRS - Inspection 0000*
12/05/2000 BUILDING - FINAL Partial Approval IVRS - Inspection 0000*
LEDGER SIESMIC WSHRS INSTALLED
LEVERS INSTALLED PER A.D.A.
08/21/2000 BUILDING - FINAL Partial Approval OK FOR TEMP C/O
SUBJECT TO OTHER INSPECTIONS
08/18/2000 BUILDING - FINAL Not ready for Inspection IVRS - Inspection 0000*
PROVIDE HANDRAILS AT INTERIOR RAMPS AS NEEDED
PROVIDE HC BARS IN TOILET ROOMS SOME FIXTURES MAY BE RELOCATED TO PROPERLY LOCATE THE HC BARS
PROVIDE AN INTERIOR LANDING AND RAMP FOR THE NORTH EAST EXIT F ROM THE WEST HALF
PROVIDE INTERIOR LANDING AND RAMP AT INTERIOR DOOR PROVIDING ACCESS TO SOUTHEAST EXIT FROM EAST PORTION OF BUIDLING TO AFFORD VISIBILITY
BOW STRING TRUSSES APPEAR TO HAVE DE LAMINATIONS AT TOP CHORD HAVE STRUCTURAL ENGINEER CERTIFY INTEGRITY OF THE TRUSS SYSTEM ALSO NOTING SPJRINKLER HEATER AND OTHER LOADS