Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/19/2000 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* OK FINAL |
|
| 09/14/2000 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* OK SUBJECT TO LETTER FROM ENGINEER REGARDING GROUND IN FEEDER RUNS |
|
| 09/11/2000 | ELECTRIC - FINAL | Partial Approval | OK TO CLEAR TEC | |
| 09/06/2000 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* 1. NEED LETTER VERIFYING TORQUE SETTING NEED LETTER VERIFING GFI TEST AS PER CODE 230-95 SECURE SERVICE ENTRANCES SECTION SUPPORT CONDUITS WITHIN 3' OF ENCLOSUER NEED LETTER FROM ENGINEER CONCERNING 3/0 GRD W/600 NOTE HAVE BUILDING INSPECTOR VERIFY BRACING FOR SERVICE SECTION CHECK GROUND CONNECTION AT GRID |