Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T00CM03606

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
03/19/2001 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
02/12/2001 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000* REAR OFFICE SECTION AND BATHROOMS
02/05/2001 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245* 1) TIE UP FIXTURE WHIPS LAYING ON T-BAR CEILING 2) T-BOX NOT MADE UP IN ROOM #112 3) 1/2" CONDUIT NOT SUPPORTED PER NEC. rOOM #111 ALSO SIZEMIC WIRE PULL OUT OF CEILING 4) TBOXES MUST BE SUPPORTED TO STRUCTURE NOT CEILING GRID ROOM #120
01/24/2001 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*
NOTES OK PORTICO
12/11/2000 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*
NORTH AND EAST SOFFITS
12/08/2000 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*
MC TYPE CABLE MUST BE SUPPORTED WITHIN 12" EACH TERMINATION POINT AND 6' INTERVALS NEC 334-10