Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/19/2001 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
| 02/12/2001 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* REAR OFFICE SECTION AND BATHROOMS | |
| 02/05/2001 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245* 1) TIE UP FIXTURE WHIPS LAYING ON T-BAR CEILING 2) T-BOX NOT MADE UP IN ROOM #112 3) 1/2" CONDUIT NOT SUPPORTED PER NEC. rOOM #111 ALSO SIZEMIC WIRE PULL OUT OF CEILING 4) TBOXES MUST BE SUPPORTED TO STRUCTURE NOT CEILING GRID ROOM #120 | |
| 01/24/2001 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* NOTES OK PORTICO |
|
| 12/11/2000 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* NORTH AND EAST SOFFITS |
|
| 12/08/2000 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245* MC TYPE CABLE MUST BE SUPPORTED WITHIN 12" EACH TERMINATION POINT AND 6' INTERVALS NEC 334-10 |