Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T00CM03606
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/08/2001 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
03/07/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245* 1) 4 SQUARE BOXES ON MASONRY WALL ARE OVER FILLED, SEE SEC. 370-16A NEC 2) SUPPORT REQUIRED WITHIN 3' OF BOX ON EMT NEC 348.13 | |
01/12/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* OK WALLS SOUTH OF SHOWROOM |
|
01/03/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* OK WALLS OFFICE AREA EXCEPT NORTH WALL |
|
12/11/2000 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* EAST SHOWROOM OFFICE PARTITIONS |
|
11/27/2000 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* (4) COLUMNS NORTH AND SHOW ROOM OK AND (1) EAST SHOWROOM COLUMS |
|
11/09/2000 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* 11/09/00 PRE SLAB FLOOR BOXES OK |
|
11/07/2000 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* UNDERGROUND ELECTRICAL BRANCH CIRCUIT CONDUITS AND FLOOR BOXES OK NORTH END OF BLD |