Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/11/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 11/01/2000 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* NEED PAPER WORK FOR SODA DISPENSER |
|
| 10/23/2000 | ELECTRIC - FINAL | Denied | 10/23/00 REMOVE BOND BAR AT SUB PANELS NEED REUSED PLANS FOR PANELS AND SERVICE DERATE FOR CONDUCTORS AT SERVICE 310-15(B) NEED TO SEE LISTING AND LABEL SODA DISPENSER TIGHTEN FITTINGS AND SECURE BOXES SEAL UNUSED HOLES IN BOXES (2) SECURE SEAL TITE TO SIGN MAINTENCE RECEPTACLE ON ROOF TO BE GFI |