Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/15/2000 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection 0000* OK TEMP SERVICE |
|
| 09/14/2000 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection 0000* NEED BOND BUSHING BOTH SIDES ON NIPPLE 250-94 STRAP CONDUIT BELOW PANEL STRAP GROUND WIRE BELOW PANEL NEED 2ND SUPPORT ON RISER AT BELOW ROOF BOND METER ENCLOUSER 250-96 |